(!)Due to Microsoft's end of support for Internet Explorer 11 on 15/06/2022, this site does not support the recommended environment.
Safety relay unit G9SA
[Features]
· Small size, with an abundant series.
· 45 mm width, with an abundant variety of 3-pole. 5-pole, 3-pole + off delay 2-pole, 2 hand controllers.
· We also offer 17.5 mm width 3-pole, off delay 3-pole expansion units.
· Expansion units can be connected with a single action.
· Off delay types can be set at 15 different time levels.
· Certified ENISO13849-1 (PLe/Safety Category 4).
· Can be DIN rail mounted or screw mounted.
Japanese Only
Part Number
Configured Part Number is shown.
| Main Contact | Auxiliary Contact | Number of Input Channels | Rated Voltage | Format |
|---|---|---|---|---|
| 3 a | 1 b | 1 ch and 2 ch shared | 24 V AC/DC | Model G9SA-301 |
| 100 to 240 V AC | ||||
| 5 a | 24 V AC/DC | Model G9SA-501 | ||
| 100 to 240 V AC |
Emergency stop unit
| Main Contact | OFF Delay Contact | Auxiliary Contact | Number of Input Channels | OFF Delay Time | Rated Voltage | Format |
|---|---|---|---|---|---|---|
| 3 a | 2 a | 1 b | 1 ch and 2 ch shared | 7.5 secs | 24 V AC/DC | Model G9SA-321-T075 |
| 15 secs | 24 V AC/DC | Model G9SA-321-T15 | ||||
| 30 secs | 24 V AC/DC | Model G9SA-321-T30 |
Emergency stop unit with OFF delay
The OFF delay time is variable in 15 steps. The following times can be set:
T075: 0.5/1/1.5/2/2.5/3/3.5/4/4.5/5/5.5/6/6.5/7/7.5 secs
T15: 1/2/3/4/5/6/7/8/9/10/11/12/13/14/15 secs
T30: 2/4/6/8/10/12/14/16/18/20/22/24/26/28/30 secs
| Main Contact | Auxiliary Contact | Number of Input Channels | Reset Mode | Input Type | Rated Voltage | Format |
|---|---|---|---|---|---|---|
| 2 a | None | 2 ch | Auto | Inverse | 24 V AC/DC | Model G9SB-2002-A |
| 1 ch, 2 ch | Positive Common | Model G9SB-200-B | ||||
| 2 ch | Manual | Inverse | Model G9SB-2002-C | |||
| 1 ch, 2 ch | Positive Common | Model G9SB-200-D | ||||
| 3 a | 1 b | No (Power supply directly OFF) | Auto | -- | 24 V DC | Model G9SB-3010 |
| 2 ch | Inverse | 24 V AC/DC | Model G9SB-3012-A | |||
| 1 ch, 2 ch | Positive Common | Model G9SB-301-B | ||||
| 2 ch | Manual | Inverse | Model G9SB-3012-C | |||
| 1 ch, 2 ch | Positive Common | Model G9SB-301-D |
| Format | Model G9SA-301 | Model G9SA-501 | Model G9SA-321-T□ |
|---|---|---|---|
| Power Supply Voltage | 24 V AC/DC: 24 V AC, 50/60 Hz / 24 V DC, 100 to 240 V AC: 100 to 240 V AC, 50/60 Hz | ||
| Allowable Voltage Fluctuation Range | Power supply voltage -15% +10% | ||
| Power Consumption | 24 V AC/DC: 1.8 VA/1.7 W max. 100 to 240 V AC: 9 VA max. | 24 V AC/DC: 2.8 VA/2.6 W max. 100 to 240 V AC: 11 VA max. | 24 V AC/DC: 3.5 VA/3.3 W max. 100 to 240 V AC: 12.5 VA max. |
Power supply: G9SA type
| Format | Model G9SB-200□-□ | Model G9SB-3010 | Model G9SB-301□-□ |
|---|---|---|---|
| Power Supply Voltage | 24 V AC/DC: 24 V AC, 50/60 Hz / 24 DC, 24 V DC: 24 V DC | ||
| Allowable Voltage Fluctuation Range | Power supply voltage -15% +10% | ||
| Power Consumption | 1.6 VA / 1.4 W max. | 1.7 W max. | 2.0 VA / 1.7 W max. |
Power supply: G9SB type
| Format | Model G9SA-301/321-T□ | Model G9SA-501 |
|---|---|---|
| Input Current | 40 mA max. | 60 mA max. |
Input: G9SA type
| Format | Model G9SB-200□-□ | Model G9SA-3010 | Model G9SB-301□-□ |
|---|---|---|---|
| Input Current | 25 mA max. | 60 mA max. | 30 mA max. |
Input: G9SB type
| Format | Model G9SA-301/501/321-T□ |
|---|---|
| Load | Resistive Load |
| Rated Load | 250 V AC 5 A, 30 V DC 5 A |
| Rated Carry Current | 5 A |
Switch: G9SA type
| Format | Model G9SB-200□-□, Model G9SB-3010, Model G9SB-301□-□ |
|---|---|
| Load | Resistive Load |
| Rated Load | 250 V AC 5 A, 30 V DC 5 A |
| Rated Carry Current | 5 A |
Switch: G9SB type
| Format | Model G9SA-301 | Model G9SA-501/321-T□ | |
|---|---|---|---|
| Contact Resistance | 100 mΩ | ||
| Operating Time | 30 ms max. | ||
| Response Time | 10 ms max. | ||
| Insulation Resistance | 100 MΩ min., 500 V DC ohmmeter | ||
| Dielectric Strength | Between Different Outputs | 2,500 V AC 50/60 Hz 1 min | |
| Between Input and Output | |||
| Between Power Supply and Output | |||
| Between Power Supply and Input (100 to 240 V AC only) | |||
| Vibration Resistance | 10 to 55 to 10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude) | ||
| Shock Resistance | Durability | 300 m/s2 | |
| Malfunction | 100 m/s2 | ||
| Durability | Mechanical | 5,000,000 operations min. (at approx. 7,200 operations/hr) | |
| Electrical | 100,000 operations min. (at 1,800 operations/hr under rated load) | ||
| Failure Rate (P Level) (Reference Value) | 5 V DC 1 mA | ||
| Ambient Operating Temperature | -25 to +55°C (assuming no icing or condensation) | ||
| Ambient Operating Humidity | 35 to 85% RH | ||
| Terminal Tightening Torque | 0.98 N·m | ||
| Weight | Approx. 210 g | Approx. 270 g | |
| Format | Model G9SB-200□-□ | Model G9SB-3010 | Model G9SB-301□-□ | |
|---|---|---|---|---|
| Contact Resistance | 100 mΩ | |||
| Operating Time | 30 ms max. | |||
| Response Time | 10 ms max. | |||
| Insulation Resistance | 100 MΩ min., 500 V DC ohmmeter | |||
| Dielectric Strength | Between Different Outputs | 2,500 V AC 50/60 Hz 1 min | ||
| Between Input and Output | ||||
| Between Power Supply and Output | ||||
| Vibration Resistance | 10 to 55 to 10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude) | |||
| Shock Resistance | Durability | 300 m/s2 | ||
| Malfunction | 100 m/s2 | |||
| Durability | Mechanical | 5,000,000 operations min. (at approx. 7,200 operations/hr) | ||
| Electrical | 100,000 operations min. (at 1,800 operations/hr under rated load) | |||
| Failure Rate (P Level) (Reference Value) | 5 V DC 1 mA | |||
| Ambient Operating Temperature | -25 to +55°C (assuming no icing or condensation) | |||
| Ambient Operating Humidity | 35 to 85% RH | |||
| Terminal Tightening Torque | 0.5 N·m | |||
| Weight | Approx. 115 g | Approx. 135 g | Approx. 120 g | |
Units: mm

Model G9SA-301
Model G9SA-501
Model G9SA-321-T□ full view

Dimensional outline drawings
Units: mm

Model G9SB-200□-□
Model G9SB-3010 full view

Dimensional outline drawings
Units: mm

Model G9SB-301□-□ full view

Dimensional outline drawings
| Part Number |
|---|
| G9SA-301 AC/DC24 |
| G9SA-321-T075 AC/DC24 |
| G9SA-501 AC/DC24 |
| G9SA-501-P DC24 |
| G9SB-2002-A AC/DC24 |
| G9SB-2002-C AC/DC24 |
| G9SB-200-B AC/DC24 |
| G9SB-200-D AC/DC24 |
| G9SB-3012-A AC/DC24 |
| G9SB-3012-C AC/DC24 |
| Part Number | Standard Unit Price | Minimum order quantity | Volume Discount | Days to Ship | Contact Configuration | Representative Standard | Dimension height (mm) | Dimension width (mm) | Dimension depth (mm) | Classification | Off delay time (Second) | Rated Voltage (V) | Reset Mode | Input Type |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
MYR 882.00 | 1 Piece(s) | 1 Day(s) | [Other] 3a1b | CE / UL / CCC / CSA | 76 | 45 | 111 | Emergency Stop Unit | - | AC/DC24 | - | - | ||
MYR 1,594.81 | 1 Piece(s) | 1 Day(s) | [Other] 3a2a1b | CE / UL / CCC / CSA | 76 | 45 | 111 | Emergency Stop Unit - With OFF Delay | 7.5 | AC/DC24 | - | - | ||
MYR 1,440.10 | 1 Piece(s) | 1 Day(s) | [Other] 5a1b | CE / UL / CCC / CSA | 76 | 45 | 111 | Emergency Stop Unit | - | AC/DC24 | - | - | ||
MYR 1,443.78 | 1 Piece(s) | 1 Day(s) | [Other] 5a1b | CE / UL / CCC / CSA | 76 | 45 | 111 | Emergency Stop Unit | - | DC24 | - | - | ||
MYR 746.00 | 1 Piece(s) | 1 Day(s) | 2a | CE / UL / TUV / CCC / CSA | 100 | 18 | 112 | Emergency Stop Unit | - | AC/DC24 | Auto | Inverse | ||
MYR 746.00 | 1 Piece(s) | 1 Day(s) | 2a | CE / UL / TUV / CCC / CSA | 100 | 18 | 112 | Emergency Stop Unit | - | AC/DC24 | Manual | Inverse | ||
MYR 746.00 | 1 Piece(s) | 1 Day(s) | 2a | CE / UL / TUV / CCC / CSA | 100 | 18 | 112 | Emergency Stop Unit | - | AC/DC24 | Auto | Positive Common | ||
MYR 746.00 | 1 Piece(s) | 1 Day(s) | 2a | CE / UL / TUV / CCC / CSA | 100 | 18 | 112 | Emergency Stop Unit | - | AC/DC24 | Manual | Positive Common | ||
MYR 940.00 | 1 Piece(s) | 1 Day(s) | [Other] 3a1b | CE / UL / TUV / CCC / CSA | 100 | 23 | 112 | Emergency Stop Unit | - | AC/DC24 | Auto | Inverse | ||
MYR 940.00 | 1 Piece(s) | 1 Day(s) | [Other] 3a1b | CE / UL / TUV / CCC / CSA | 100 | 23 | 112 | Emergency Stop Unit | - | AC/DC24 | Manual | Inverse |
Loading...
| Application | Safety relay | Latch function | NA | Terminal shape | Screw Fastening |
|---|


OMRON
Standard Price : MYR 644.56
Days to Ship : 1 Day(s)




How can we improve?
How can we improve?
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Customer Privacy Policy
Thank you for your cooperation.
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Please use the inquiry form.
Customer Privacy Policy